FGARD UVIR

The Crowcon FGard UVIR flame detector is an explosion-proof ultraviolet-infrared flame detector, offering superior detection of hydrocarbon fires which are not detectable in the visible spectrum. With adjustable sensors, the Fgard UVIR can be adapted to suit your space, and is capable of operating in even the harshest conditions.

Product Datasheet

Category: Brand:

Tailor made to detect hydrocarbon flames outside the visible spectrum, the FGard UVIR flame detector is an explosion proof ultraviolet-infrared flame detector designed to provide elite detection of hydrocarbon fires.

The Fgard UVIR incorporates the latest IR flame detection algorithms to prevent the risk of false alarms, and with three different sensitivity settings, you can customise the sensors for your space and needs.
Designed to operate in all conditions, the microprocessor controlled heated optics ensure continuous operation even in harsh weather environments at risk of snow, ice, and condensation.

With advanced optical verification, an automatic test verifies cleanliness of the lens and electronic circuitry to ensure the detector is always primed for optimal performance, requiring no reflector optical check. Plus, its large optical surface minimises the risk of false alarms, so you can respond efficiently with confidence to any alarm.

Operating temp -60°C to +85°C (-76°F to +185°F)
Storage temp -76°F to +185°F (-60°C to +85°C)
Humidity 0-100 % RH (Non-condensing)
Operating voltage 24 Vdc Nominal – (Range 18 to 32 Vdc)
Power consumption 3W minimum (without heater), 15 W at 32 Vdc with heater on maximum.
Speed of response < 5 seconds (Typical)
Dimensions 100 mm Dia x 200 mm (4” Dia x 8” L)
Material Copper free aluminum or 316 stainless steel
Entry size 3/4 inch NPT or M25
Weight Alu 5.5 lbs (2.5 Kg) / SS 13.2 lbs (6.0kg)
Outputs Relay contacts (DPDT 2A at 30Vdc) – alarm and fault.
0-20mA plus fault alerts, HART®
Certifications Class 1 Div 1 Groups B, C, D T4 Ambient –50°C to +85°C
Class 1 Zone 1 AEx/Ex db IIC T4 Ambient –50°C to +85°C
ATEX II 2 G Ex db IIC T4
IECEx Ex db IIC T4 Ambient –60°C to +85°C
INMETRO Ex db IIC T4 – pending
PESO Ex db IIC T4 Ta= -60°C to +85°C – pending
Performance approvals FM 3260
EN 54-10
Ingress – IP67 /NEMA type 6P
*SIL2 certified pending – IEC 61508