FGARD IR3

The Crowcon Fgard IR3 flame detector is an explosion proof multi spectrum infrared (IR) flame detector, responding to hydrocarbon liquid fuel and gas fires even at long distances. The Fgard IR3 delivers first-in-class flame detection, with intelligent heated optics for clearer results and advanced optical verification to greatly reduce false alarms.

ورقة بيانات المنتج

التصنيف: الوسم: العلامة التجارية:

The Fgard IR3 delivers superior performance in the detection of hydrocarbon fires, using the latest infrared (IR) flame detection algorithms to minimise the risk of false alarms.

The Fgard IR3 has been independently tested to demonstrate it can detect a hydrocarbon fuel pan fire at nearly 200 feet in less than 5 seconds, maximising the time you have to respond in an emergency.

Its multi-spectrum IR will detect all hydrocarbon fires with intelligent heated optics, meaning no condensation, ice or water affecting detection. Plus, its advanced optical verification checks cleanliness of the lens and electronic circuitry, meaning no reflector optical check is needed, and a large optical surface results in far fewer false alarm

Operating temp -60°C to +85°C (-76°F to +185°F)
Storage temp -76°F to +185°F (-60°C to +85°C)
Humidity 0-100 % RH (Non-condensing)
Operating voltage 24 Vdc Nominal – (Range 18 to 32 Vdc)
Power consumption 3W minimum (without heater), 15 W at 32 Vdc with heater on maximum.
Speed of response < 5 seconds (Typical)
Dimensions 100 mm Dia x 200 mm (4” Dia x 8” L)
Material Copper free aluminum or 316 stainless steel
Entry size 3/4 inch NPT or M25
Weight Alu 5.5 lbs (2.5 Kg) / SS 13.2 lbs (6.0kg)
Outputs Relay contacts (DPDT 2A at 30Vdc) – alarm and fault.
0-20mA plus fault alerts, HART®
Certifications Class 1 Div 1 Groups B, C, D T4 Ambient –50°C to +85°C
Class 1 Zone 1 AEx/Ex db IIC T4 Ambient –50°C to +85°C
ATEX II 2 G Ex db IIC T4
IECEx Ex db IIC T4 Ambient –60°C to +85°C
INMETRO Ex db IIC T4
PESO Ex db IIC T4 Ta= -60°C to +85°C
CCC (China Fire Approvals) – Pending
GB-Ex of China – Pending
Performance approvals FM 3260
EN 54-10
Ingress – IP66 /NEMA 4X
SIL2 certified – IEC 61508